SHEET: 2 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
FMS Sensor Wiring Guide
10061_FMS Rev 2.0 (8/13)
FMS to T120D Integration
P1
VDC
TB 1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB 2 Inp ut 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB 3 Inp ut 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB 4
NC NO C
RELAY 1
NC NO C
RELAY 2
PWR(4-20 S END)
COMMON
RH OUT (4-20 RTN)
T OUT (4-20 RTN)
RTD/OVERRIDE
RTD/OVERRIDE
SLIDER RIGHT
SLIDER WIPER
SLIDER LEFT
BACK P IECE CENT ER PIECE (WITH CIRCUIT BOARD)
SW1
mAVolts
TEMP 10/5V
TEMP RA NGE
50-95/32-122
TEMP F/C
Out put Select
Figure 2.2: 50-95F Range Setup
Figure 2.3: 32-122F Range Setup
RH 10/5V
1. Set the switch position to mA. Set the temperature range to
50-95 or 32-122. The sensor is shipped from the factory with
the switch in the volts position and the temperature range is
set for 50-95F. The switch position must be set to the mA
position.
2. Wire the sensor to the CH # being used.
4. Verify the "Calc" value displays the correct room temperature.
The temperature can also be viewed on the Falcon main page.
SETUP
1. Calculate the T120D Output current for temperature.
TROUBLESHOOTING
2. Measure the current flowing into the Falcon Ch- terminal with a
current meter. Verify that it is close to the calculated current (+/-
1%).
3. If measured current does not match calculated current then
check wiring and check T120D jumper and switch
settings.
4. Compare the measured current matches the current reading in
the Falcon.
5. Check the wiring if the Falcon current reading does not match
the measured current reading.
6. If the Falcon current reading matches the measured current
and the Falcon Calculated value does not match the room
temperature then the offset and gain values are wrong.
Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees
above or below the room temperature then adjust the offset by
1 or 2. Do not adjust the gain. Only tweak the offset once the
previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature
contact RLE Technologies technical support at 970.484.6510.
Figure 2.1: FMS Wiring with the T120D
1
3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the Gain and offset values. For the 50-95F
range use Gain 11.25, Offset 38.75. For 32-122F range use
Gain 22, Offset 10.
2
3
3
Example if Room Temp is 70F and your sensor has a range of 50-95
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
Formula for calculating the correct RAW value
4
4